logo
Chất lượng 0-10MΩ Insulation Monitoring Device Power Supply Equipment DC24V~1500V nhà máy
<
Chất lượng 0-10MΩ Insulation Monitoring Device Power Supply Equipment DC24V~1500V nhà máy
Chất lượng 0-10MΩ Insulation Monitoring Device Power Supply Equipment DC24V~1500V nhà máy
>

0-10MΩ Insulation Monitoring Device Power Supply Equipment DC24V~1500V

Tóm tắt sản phẩm

Insulation Testing Device with 0-10 MΩ Monitoring Range Dual-Bus Monitoring and Hierarchical Alarms for Accurate Fault Detection Insulation Testing Device Functional Features Monitoring range: 0-10 MΩ (extendable up to 100 MΩ), accuracy ±5%, resolution ≤1 kΩ Dual-bus monitoring: Independently ...

Thuộc tính tùy chỉnh sản phẩm

Phạm vi điện trở cách nhiệt:
0,1kΩ~10MΩ
Độ chính xác của phép đo:
±0,5% (toàn dải)
Phạm vi giám sát điện áp:
DC 24V~1500V
Thời gian đáp ứng:
5 giây (quét toàn hệ thống)
Điện áp làm việc:
DC85V~265V
Nhiệt độ làm việc:
-40 ~+70
Làm nổi bật:

10MΩ Insulation Monitoring Device

,

Power Supply Equipment DC24V

,

1500V Insulation Monitoring Device

Thuộc tính cơ bản

Nguồn gốc:
Thâm Quyến, tỉnh Quảng Đông, Trung Quốc
Hàng hiệu:
Shenzhen Hongyi Technology Co.,Ltd
Số mô hình:
SH-INSM

Giao dịch Bất động sản

Số lượng đặt hàng tối thiểu:
1
Giá bán:
RMB 1499
Thời gian giao hàng:
10-14 ngày làm việc
Điều khoản thanh toán:
T/T
Khả năng cung cấp:
30

Mô tả sản phẩm

Insulation Testing Device with 0-10 MΩ Monitoring Range Dual-Bus Monitoring and Hierarchical Alarms for Accurate Fault Detection

 

Insulation Testing Device
Functional Features
  • Monitoring range: 0-10 MΩ (extendable up to 100 MΩ), accuracy ±5%, resolution ≤1 kΩ
  • Dual-bus monitoring: Independently measures insulation resistance between positive and negative electrodes to ground
  • Supports hierarchical alarms (early warnings and alerts) with customizable thresholds
  • Branch circuit inspection: Identifies faulty insulated branches using sampling resistor switching
  • Distinguishes between fault types including single-pole grounding and bipolar unbalanced grounding
  • Adaptive monitoring mode: Automatically adjusts measurement modes based on system voltage fluctuations
  • Supports host, extension, and slave operation modes
  • Supports coordinated testing of system interconnection faults between master and slave devices
  • Supports main handset mode for split-screen designs
  • Compatible with both digital and analog leakage current sensors
  • Modular design with parameter import via USB drive
  • Flexible configuration: Integrates with DC monitoring devices or standalone human-machine interface
  • Automatic switching of bridge resistor values for 110V/220V system adaptation
Technical Specifications
Monitoring Parameters
Parameter Item Typical Value/Range Description
Insulation resistance measurement range 0.1kΩ~10MΩ High-resistance range for high-voltage systems (photovoltaic, energy storage); low-resistance range for precise alarms
Measurement accuracy ±0.5% (full range) High-precision design ensures reliable leakage current warning performance
Voltage Monitoring Range DC 24V~1500V Compatible with wide voltage ranges including communication base stations (48V), substations (220V), and photovoltaic systems (1500V)
Resolution ≤1 kΩ (insulation resistance); ≤0.1 V (bus voltage) High resolution enables analysis of subtle insulation degradation trends
Response time ≤5 seconds (system-wide scan) Quickly detect insulation degradation with branch localization time ≤30 seconds
Fault Localization and Performance Parameters
Parameter Item Typical Value/Range Description
Branch positioning accuracy ±5% (insulation resistance)  
Fault Type Identification Unipolar grounding, bipolar unbalanced grounding, capacitive grounding  
Capacitive Compensation Function Supports ground capacitance ≤ 100 μF  
Communication and Interface Parameters
Parameter Item Typical Value/Range Description
Communication Interface RS485 Supports Modbus RTU protocol
Alarm Output Dry contact signal (passive contact) Always-on/always-off contact, rated capacity 250 V AC/5 A, directly drives relay or audio-visual alarm
Data storage ≥100,000 event records Stores historical insulation resistance data and fault events with timestamps; supports export to USB drives
SOE resolution ≤1ms Records sequence of fault occurrences for multi-system collaborative analysis
Electrical and Environmental Adaptability
Parameter Item Typical Value/Range Description
Working voltage DC85V~265V Wide voltage input, compatible with 110V/220V DC systems
Power 12V60W Supports power supply for up to 720 digital CT units
Working temperature -40℃~+70℃  
Safety and Reliability Parameters
Parameter Item Typical Value/Range Description
Isolation Voltage ≥2500 V AC Between input, output, and communication circuits; suppresses transient overvoltages from surges or lightning strikes
Surge protection 8/20 μs surge current: 20 kA (IEC 61000-4-5) Prevents equipment damage caused by wiring errors
Self-checking function Power-on self-test (bridge arm resistance, ADC, communication) Ensures long-term equipment reliability