0-10MΩ Insulation Monitoring Device Power Supply Equipment DC24V~1500V
제품 요약
Insulation Testing Device with 0-10 MΩ Monitoring Range Dual-Bus Monitoring and Hierarchical Alarms for Accurate Fault Detection Insulation Testing Device Functional Features Monitoring range: 0-10 MΩ (extendable up to 100 MΩ), accuracy ±5%, resolution ≤1 kΩ Dual-bus monitoring: Independently ...
제품 맞춤 속성
절연 저항 범위:
0.1kΩ~10MΩ
측정 정확도:
±0.5%(전체 범위)
전압 모니터링 범위:
DC 24V~1500V
응답 시간:
5초 이하(시스템 전체 스캔)
작동 전압:
DC85V~265V
작동 온도:
-40+~+70 ℃
강조하다:
10MΩ Insulation Monitoring Device
,Power Supply Equipment DC24V
,1500V Insulation Monitoring Device
기본 특성
원래 장소:
심천, 광둥성, 중국
브랜드 이름:
Shenzhen Hongyi Technology Co.,Ltd
모델 번호:
SH-INSM
부동산 거래
최소 주문 수량:
1
가격:
RMB 1499
배달 시간:
10-14 작업 일수
지불 조건:
티/티
공급 능력:
30
제품 설명
Insulation Testing Device with 0-10 MΩ Monitoring Range Dual-Bus Monitoring and Hierarchical Alarms for Accurate Fault Detection
Insulation Testing Device
Functional Features
- Monitoring range: 0-10 MΩ (extendable up to 100 MΩ), accuracy ±5%, resolution ≤1 kΩ
- Dual-bus monitoring: Independently measures insulation resistance between positive and negative electrodes to ground
- Supports hierarchical alarms (early warnings and alerts) with customizable thresholds
- Branch circuit inspection: Identifies faulty insulated branches using sampling resistor switching
- Distinguishes between fault types including single-pole grounding and bipolar unbalanced grounding
- Adaptive monitoring mode: Automatically adjusts measurement modes based on system voltage fluctuations
- Supports host, extension, and slave operation modes
- Supports coordinated testing of system interconnection faults between master and slave devices
- Supports main handset mode for split-screen designs
- Compatible with both digital and analog leakage current sensors
- Modular design with parameter import via USB drive
- Flexible configuration: Integrates with DC monitoring devices or standalone human-machine interface
- Automatic switching of bridge resistor values for 110V/220V system adaptation
Technical Specifications
Monitoring Parameters
| Parameter Item | Typical Value/Range | Description |
|---|---|---|
| Insulation resistance measurement range | 0.1kΩ~10MΩ | High-resistance range for high-voltage systems (photovoltaic, energy storage); low-resistance range for precise alarms |
| Measurement accuracy | ±0.5% (full range) | High-precision design ensures reliable leakage current warning performance |
| Voltage Monitoring Range | DC 24V~1500V | Compatible with wide voltage ranges including communication base stations (48V), substations (220V), and photovoltaic systems (1500V) |
| Resolution | ≤1 kΩ (insulation resistance); ≤0.1 V (bus voltage) | High resolution enables analysis of subtle insulation degradation trends |
| Response time | ≤5 seconds (system-wide scan) | Quickly detect insulation degradation with branch localization time ≤30 seconds |
Fault Localization and Performance Parameters
| Parameter Item | Typical Value/Range | Description |
|---|---|---|
| Branch positioning accuracy | ±5% (insulation resistance) | |
| Fault Type Identification | Unipolar grounding, bipolar unbalanced grounding, capacitive grounding | |
| Capacitive Compensation Function | Supports ground capacitance ≤ 100 μF |
Communication and Interface Parameters
| Parameter Item | Typical Value/Range | Description |
|---|---|---|
| Communication Interface | RS485 | Supports Modbus RTU protocol |
| Alarm Output | Dry contact signal (passive contact) | Always-on/always-off contact, rated capacity 250 V AC/5 A, directly drives relay or audio-visual alarm |
| Data storage | ≥100,000 event records | Stores historical insulation resistance data and fault events with timestamps; supports export to USB drives |
| SOE resolution | ≤1ms | Records sequence of fault occurrences for multi-system collaborative analysis |
Electrical and Environmental Adaptability
| Parameter Item | Typical Value/Range | Description |
|---|---|---|
| Working voltage | DC85V~265V | Wide voltage input, compatible with 110V/220V DC systems |
| Power | 12V60W | Supports power supply for up to 720 digital CT units |
| Working temperature | -40℃~+70℃ |
Safety and Reliability Parameters
| Parameter Item | Typical Value/Range | Description |
|---|---|---|
| Isolation Voltage | ≥2500 V AC | Between input, output, and communication circuits; suppresses transient overvoltages from surges or lightning strikes |
| Surge protection | 8/20 μs surge current: 20 kA (IEC 61000-4-5) | Prevents equipment damage caused by wiring errors |
| Self-checking function | Power-on self-test (bridge arm resistance, ADC, communication) | Ensures long-term equipment reliability |