logo
品質 220V 110V DC Power Supply Cabinet IEC103 IEC61850 Industrial DC Power Supply 工場
<
品質 220V 110V DC Power Supply Cabinet IEC103 IEC61850 Industrial DC Power Supply 工場
>

220V 110V DC Power Supply Cabinet IEC103 IEC61850 Industrial DC Power Supply

製品概要

Intelligent DC Power Supply System with Busbar Voltage Loss Compensation, Battery Health Monitoring, and Modularized Power Supply Unit Intelligent DC Power Supply System System Overview The intelligent DC power supply system integrates an AC distribution unit, charging module, feeder unit, battery ...

製品カスタム属性

AC入力電圧:
323V~456V
AC入力周波数:
45Hz~55Hz
力率:
>0.92
DC 定数電圧:
110V(220V)
定常流量精度:
≤0.5%
リップルファクター:
≤0.1%
ハイライト:

110V DC Power Supply Cabinet

,

DC Power Supply Cabinet IEC103

,

IEC61850 Industrial DC Power Supply

基本プロパティ

ブランド名:
Shenzhen Hongyi Technology Co.,Ltd

取引物件

最小注文数量:
1
価格:
RMB 29999 per set
受渡し時間:
10-14の仕事日
支払条件:
T/T
供給の能力:
10

製品説明

Intelligent DC Power Supply System with Busbar Voltage Loss Compensation, Battery Health Monitoring, and Modularized Power Supply Unit

 

Intelligent DC Power Supply System
System Overview

The intelligent DC power supply system integrates an AC distribution unit, charging module, feeder unit, battery bank, monitoring unit, voltage and current monitoring instruments, insulation monitoring device, silicon-based voltage reduction circuit, and battery management unit. It serves as a critical component of substation power systems and power plants, providing power for automatic control, power equipment, relay protection, instrumentation, signaling, communication, and emergency lighting systems.

Applications

The DC power supply system is applied in large, medium, and small power plants as well as substations, providing the necessary DC power for high-voltage switch operations (opening/closing), relay protection, automatic control, emergency lighting, illumination, and signaling during both normal operation and fault conditions.

It also serves industries such as metallurgy, railways, mining, petrochemicals, postal services, telecommunications, healthcare, banking, hotels, high-rise buildings, and computer networks. This product complies with the JB/T 57774-2000 standard "General Technical Requirements and Safety Requirements for DC Power Equipment in Power Systems".

System Functional Features
  • Busbar voltage loss compensation: In the event of a DC busbar voltage failure, adaptive zero-delay switching can be activated online to ensure continuous power supply and enhance the self-healing capability of the DC power system.
  • Battery health monitoring: Proactively prevents DC bus power failure caused by internal open circuits in the battery; actively addresses DC bus voltage loss faults resulting from inherent battery defects.
  • Automatic capacity verification: Automates battery capacity verification locally or remotely, reducing personnel requirements.
  • Intelligent diagnostic decision-making: Comprehensive intelligent detection and diagnosis of power equipment.
  • Comprehensive status monitoring: Effectively detects whether the battery has disconnected from the busbar, preventing operations that may cause voltage loss on the DC busbar.
  • Modularized power supply unit: The switch unit consists of a feeder circuit breaker, leakage current transformer (CT), signal lights, data acquisition board, and drawer-type structure, enabling replacement of the switch unit without power interruption.
Electrical Characteristics
Order Number Project Technical Requirement
1 AC Input Power Source 323V~456V
2 AC Input Frequency 45Hz~55Hz
3 Power Factor >0.92
4 Asymmetry of the AC Input Voltage ≤5%
5 Percentage of Each Harmonic Current Component (2nd to 19th Order) <30%
6 Nominal Voltage of the DC Power Supply System (Un) 110V(220V)
7 Normal Operating Voltage of the DC Control Busbar 115.5V(231V)
8 Charging Voltage Adjustment Range (90%~125%)Un
9 DC Control Bus Voltage Range (85%~112.5%)Un
10 DC Power Bus Voltage Range (87.5%~17.5%)Un
11 Steady Flow Accuracy ≤0.5% (when operating at 20–100% of the rated output current)
12 Voltage Stabilization Accuracy ≤0.5% (when outputting rated current from 0% to 100%)
13 Flow Distribution Imbalance ≤±3%
14 Ripple Factor ≤0.1%
15 Productiveness >93%
16 Noise ≤55 dB (at a distance of 1 m from the device)
17 Cooling Method Use natural cooling or forced air cooling
18 Time Interface IRIG-B code and software synchronization
19 Communication Interface RS485/RS232 communication interfaces and Ethernet communication interfaces
20 Communication Protocol IEC 103, IEC 61850, MODBUS protocol